Weekly Fire Alarm Testing

Manual Call Point Operating Guidance

This document provides guidance on operating the different types of manual call point (MCP) present on campus as part of the weekly fire alarm test. In some buildings the MCPs will all be of the same type while in others there may be a mixture. A different MCP should be tested each week on rotation as part of the test.

For further information on the weekly fire alarm test, please refer to this guidance note:

Type One MCP

Type One MCP
The red key required for testing.

1. Open Cover

Slide up the cover to expose the testing keyhole.

2. Activate

Insert the test key and turn clockwise. This will activate the call point and trigger the alarm sounders.

When the key is turned clockwise the yellow flag drops down to show that the MCP has been activated.

3. Deactivate

Once the sounders have activated, turn the key anti clockwise.

When the key is turned back anti clockwise, the yellow flag retracts back into the MCP.

4. Remove Key

Remove the test key and slide the cover down.

The MCP is back to normal mode and the test is complete.

Type Two MCP

Type 2 MCP
The black key required for testing

1. Insert the key

Insert the double pronged end of the key into the testing slot under the MCP. Once the key is fully engaged into the MCP you will hear it click.

The testing slot is located centrally under the MCP.

2. Pull down the Key

Pull the key down towards the floor. The front of the MCP will drop down, activating the alarm and triggering the sounders.

The yellow area is exposed when the MCP is activated.

4. Remove the Key

Once the sounders have activated, remove the testing key

It is easier to click the front of the MCP back into position once the testing key has been removed.

5. Push up the Front

Push the front of the MCP back up. It will click when fully engaged in the correct position.

The MCP is back to normal mode and the test is complete.

Type Three MCP

MCP3
The black key required for testing.

1. Insert the Key

Insert the testing key in the testing slot underneath the MCP.

The L-shaped testing slot is located underneath the MCP.

2. Drop the Glass

Push the key into the MCP until a click is heard and the glass drops down.

The glass is no longer sitting straight within the MCP.

3. Remove the Key

Remove the testing key.

The glass has clicked back into position. The MCP is back to normal mode and the test is complete.

Type Four MCP

The long black key required for testing

1. Insert the Key

Insert the testing key into the testing slot underneath the MCP.

The testing slot is located at the side underneath the MCP.

2. Activate the Sounders

Fully insert the testing key. This will activate the MCP and trigger the sounders.

The glass is tilted backward at the top and is no longer sitting straight within the MCP.

3. Remove the Key

Remove the testing key.

The glass has clicked back into position. The MCP is in normal mode and the test is complete.