Honeywell Pearle Notifier

Fire Alarm Panel Operating Instructions

This document provides operating instructions for performing the weekly fire alarm test and resetting after an activation on the Honeywell Pearle Notifier fire panel.

Weekly Fire Alarm Test

Ensure that Security are notified before the test begins and again once the test is complete.

For further information on the weekly fire alarm test, please refer to guidance note ‘Fire Alarm Weekly Test’ 

1. Before the test begins

Before the test begins, the fire panel will be in normal mode:

The LED display panel is showing the home screen. The green power light is illuminated.

3. Open the Fire Panel

Open the fire panel using key 901.

4. Activate a Manual Call Point

Activate a manual call point using a black testing key. The Fire Panel will now be in fire mode.

The LED display screen is showing the location of the activation. The red fire light is illuminated along with the red lights showing the zones that have been evacuated.

5. Press the "Mute" Button

6. Press the "Silence" Button

7. Press the "Reset" Button

The fire panel will return to normal mode:

8. Lock the Fire Panel

Lock the fire panel using key 901.

9. Lock the fire panel using key 901

10. Re-enable any plant

Re-enable any plant that was isolated during the test at the plant isolation switch.

Re-setting After an Activation

Once an investigation has been undertaken and it has been confirmed there is no fire:

  • Open the fire panel using key 901.
  • The LED display screen will show the location of the activation. The red fire light will be illuminated along with the red zone lights showing the location of the activation.
  • Press the ‘Mute’ button.
  • Press the ‘Silence Alarms’ button
  • Press the ‘Reset’ button

 

The panel should return to normal mode.

Lock the panel using key 901.

Remember to reset any plant linked to the fire alarm as it may have tripped or isolated when the fire alarm activated.

If the alarm will not reset, investigate the area again. If the alarm is confirmed to be false, silence the alarm but do not reset it. Call Security and request that they contact the duty electrician