Climac ZP3
Fire Alarm Panel Operating Instructions
This document provides operating instructions for performing the weekly fire alarm test and resetting after a fire alarm activation on the Clymac ZP3 fire panel.
Weekly Fire Alarm Test
Ensure that Security are notified before the test begins and again once the test is complete.
For further information on the weekly fire alarm test, please refer to guidance note:
1. Before the test begins
Before the test begins, the fire panel will be in normal mode:
The panel display is showing the date, time and building name. Only the green power light is illuminated.
3. Activate a Manual Call Point
Activate a manual call point using a black testing key. The Fire Panel will now be in fire mode.
The panel display is showing that there is an active fire alarm in progress and the zone location of the alarm. The red fire light is illuminated along with a red light for the activated zone and the three red lights indicating the active features.
4. Press "Silence Arms"
The panel will then prompt you to enter a code:
5. Input Code
Input code 2000 using the numbers on the keypad. Then press the enter/curved arrow button on the keypad. This will enable the fire panel allowing you to reset the alarms. You need to press the keypad buttons firmly.
Input the code 2000 then press RETURN
6. Press "Accept"
7. Press "Reset"
The panel should return to normal mode:
The panel display is showing the date, time and building name. Only the green power light is illuminated.
8. Re-enable any Plant
Enable any plant that was isolated during the test at the plant isolation switch.
Re-setting After an Activation
Once an investigation has been undertaken and it has been confirmed there is no fire:
- Press ‘Silence Alarms.’ The alarm will silence after a few seconds.
- Input code 2000 using the numbers on the keypad. Then press the enter/curved arrow button on the keypad. This will enable the fire panel allowing you to reset the alarms. You need to press the keypad buttons firmly.
- Press ‘Accept.’
- Press ‘Reset.’
The panel should return to normal mode.
Remember to reset any plant linked to the fire alarm as it may have tripped or isolated when the fire alarm activated.
If the alarm will not reset, investigate the area again. If the alarm is confirmed to be false, silence the alarm but do not reset. Call Security and request that they contact the duty electrician.